Add to Cart
Central Air Cooled Screw Chiller , High effiency Chiller 380V/ 3ph / 50Hz
Air cooled chillers absorb heat from process water, and the heat is then transferred to the air around the
chiller unit. This type of chiller system is generally used in applications where the additional heat it discharges
is not a factor. In fact, it's often practical to use the excess heat to warm a plant during the winter, thus
providing additional cost savings.
Air Cooled Chillers Vs Water Cooled Chillers
1. Air cooled chillers require less maintenance than water-cooled units.
2. Air cooled chillers do not require a cooling tower or a condenser water pump.
3. Consume approximately 10% more power than a water-cooled unit due to wet surfaces transferring heat better than dry surfaces.
1. Features:
1. Using imported international brands Germany (), HANBELL China Taiwan energy efficient
compressor matches the quality of the condenser and evaporator, high efficiency, stable performance, Low
noise, long service life Industrial PLC central control unit, the energy transfer system with the compressor
can be timely efficiency in order to run the unit, lower operating costs;
2. Within the integrated water, low temperature, high pressure, freezing, phase, delay start, reverse, overload,
motor overheating, oil pressure, and poor treatment a number of security features;
3. English user interface, menu prompts, can be set unit operating environment;
4. Volume control can be four sections (100%-75%-50%-25%) or three-step (100%-66%-33%) and non-stage control systems;
5. A unique built-in hydraulic system, no pumps are guaranteed to maintain the best lubricating effect of the
compressor, oil separator with double filtration, oil filtering effect of good, can play a maximum capacity of
heat exchangers;
6. Efficient thread copper tube to enhance heat transfer effects, more energy efficient. Using the latest
CAD/CAM design and processing technology CNC machining center produced, compact structure, small
volume, durable. U-beam structure of the tubes can be cleaned out within the overall scale, easy maintenance,
to prevent refrigerant leakage phenomenon;
7. Use all imports of the corrugates steel pipe and hyperbolic hydrophilic aluminum foil, high-speed drilling,
and other professional equipment manufacturers, is more closely exposed pipe and fin, heat transfer more
efficient, with a small size, light weight, the advantages of more compact and reasonable; 8. No need to install
cooling towers, cooling water pumps and other equipment for water scarcity and poor water quality areas.
It can be installed on the roof, rooftops and other open spaces, no special room is needed, saving space;
2. Specification:
Air cooled Screw Chiller | |||||||||
Model HLWA~ |
| 110S | 160S | 210S | 240S | 280S | 310S | 340S | |
| X 1000Kcal/h | 93.6 | 133.6 | 178.7 | 210.6 | 243.4 | 263.5 | 290.1 | |
KW | 109 | 155 | 208 | 245 | 283 | 307 | 337 | ||
Comp. lnput Power×Qty (KW) | 34.7×1 | 47.7×1 | 63.2×1 | 71.2×1 | 82.4×1 | 89.9×1 | 99.9×1 | ||
Refrigerant | R407C | ||||||||
Power Supply | 380V/ 3ph/ 50Hz | ||||||||
Safety Protection |
Overload current protection, pressure protection, Low temp. protection, Water flow protection. | ||||||||
Number of Refrigeration Circuit | 1 | ||||||||
Capacity Control (%) | 0, 50, 75, 100 | ||||||||
Refrigerant Charge (Kg) | 30 | 42 | 56 | 68 | 78 | 84 | 93 | ||
Condenser | Ripple Aluminum Fins Around Copper Pipe | ||||||||
| Dia.of Pipe (inch) | 2-1/2" | 3" | 3" | 3" | 4" | 4" | 4" | |
| 1 | ||||||||
| 18.7 | 26.7 | 35.7 | 42.1 | 48.7 | 52.7 | 58.0 | ||
Water Pressure drop (kPa) | 28 | 33 | 48 | 55 | 61 | 64 | 66 | ||
|
| 56.8 | 80.4 | 113.6 | 115.2 | 115.2 | 160.8 | 160.8 | |
Power×Qty (KW) | 1.2×4 | 2.0×4 | 1.2×8 | 1.2×8 | 1.2×8 | 2.0×8 | 2.0×8 | ||
Running Noise dB(A) | 68 | 68 | 68 | 68 | 72 | 72 | 72 | ||
Total Weight (Kg) | 1160 | 1730 | 2590 | 2670 | 2750 | 2930 | 3160 | ||
Running Weight(Kg) | 1270 | 1920 | 2810 | 2900 | 3020 | 3240 | 3450 |
3. Air cooled screw chiller photo